Uploaded image for project: 'ZABBIX BUGS AND ISSUES'
  1. ZABBIX BUGS AND ISSUES
  2. ZBX-22085

Mellanox template does not detect power loss on PSU

XMLWordPrintable

    • Icon: Problem report Problem report
    • Resolution: Unresolved
    • Icon: Trivial Trivial
    • None
    • 6.0.12
    • Templates (T)

      Steps to reproduce:

      1. Create a host and apply  Mellanox by SNMP template 
      2. Remove power cable from a Mellanox PSU 

      Result:
      No problems triggered
      Expected:
      A problem is triggered

      Cause:

      The item prototype in PSU discovery refers to an OID which does not change its value when a power loss occurs. It seems always reporting the value: enabled (2).

       

      Proposed solution

      As Mellanox support team suggested, use entStateAlarm oid:

      Additional note

      In our environment we kept both items and triggers, to be safe.

            zit Zabbix Integration Team
            bitmind Nicola Mauri
            Votes:
            0 Vote for this issue
            Watchers:
            2 Start watching this issue

              Created:
              Updated: