Improve support SNMP BITS without a MIB

XMLWordPrintable

      ZBXNEXT-8246 added "Integer from BITS" preprocessing step, which great.

      But in reality I get this:

      iso.2.840.10006.300.43.1.2.1.1.23.1 = STRING: "="
      iso.2.840.10006.300.43.1.2.1.1.23.1 = STRING: "="
      iso.2.840.10006.300.43.1.2.1.1.23.2 = STRING: "="
      iso.2.840.10006.300.43.1.2.1.1.23.3 = STRING: "="
      iso.2.840.10006.300.43.1.2.1.1.23.4 = Hex-STRING: 00
      iso.2.840.10006.300.43.1.2.1.1.23.5 = STRING: "="
      iso.2.840.10006.300.43.1.2.1.1.23.6 = STRING: "="
      iso.2.840.10006.300.43.1.2.1.1.23.7 = STRING: "="
      iso.2.840.10006.300.43.1.2.1.1.23.8 = STRING: "="
      

      I understand rfc3417#section-8 uses OCTET-STRING both for BITS and for STRING so snmp tools have to guess (or be forced by -Oa or -Ox).

      Can this be resolved by allowing "Integer from BITS" preprocessing to work on STRING values so it works regardless of how snmp tools's guess goes?

      Thank you.