Thresholds for some metrics on Cisco Catalyst 4500 (and others) are too low

XMLWordPrintable

    • Icon: Change Request Change Request
    • Resolution: Unresolved
    • Icon: Trivial Trivial
    • None
    • 7.0.0alpha9
    • Templates (T)
    • None
    • Tested on 6.4.7 but template has no changes on this aspect on current master

      On Cisco IOS by SNMP template, there are three temperature triggers

              - '{$TEMP_CRIT}' value: '60'
              - '{$TEMP_CRIT:"CPU"}' value: '75'
              - '{$TEMP_CRIT_LOW}' value: '5'

      But the sensors on a properly functioning system report higher thresholds for some of the values (values on column temperature between parentheses are for minor,major or critical values)

      {{#sh environment temperature  

      Module Sensor                     Temperature          Status       
      ------+--------------------------+--------------------+------------ 
      1      air inlet                  31C (45C,60C,70C)              ok 
      1      air outlet                 37C (61C,76C,86C)              ok 
      2      air inlet                  29C (45C,60C,70C)              ok 
      2      air outlet                 35C (61C,76C,86C)              ok 
      3      Air inlet                  32C (56C,68C,71C)              ok 
      3      Air inlet remote           25C (46C,59C,62C)              ok 
      3      Air outlet                 32C (66C,76C,79C)              ok 
      3      Air outlet remote          27C (60C,71C,74C)              ok 
      5      Air inlet                  25C (50C,66C,72C)              ok 
      5      Air outlet                 46C (73C,80C,92C)              ok 
      5      XPP                        73C (101C,120C,123C)           ok 
      5      IFE                        40C (65C,90C,120C)             ok 
      5      CONAN                      47C (67C,82C,100C)             ok 
      5      CPU                        45C (69C,102C,105C)            ok 
      6      Air inlet                  24C (50C,66C,72C)              ok 
      6      Air outlet                 45C (73C,80C,92C)              ok 
      6      XPP                        71C (101C,120C,123C)           ok 
      6      IFE                        37C (65C,90C,120C)             ok 
      6      CONAN                      46C (67C,82C,100C)             ok 
      6      CPU                        37C (69C,102C,105C)            ok 
      7      Air inlet                  27C (44C,59C,62C)              ok 
      7      Air inlet remote           28C (47C,61C,64C)              ok 
      7      Air outlet                 30C (47C,62C,65C)              ok 
      7      Air outlet remote          32C (52C,66C,69C)              ok 
      8      air inlet                  25C (41C,56C,66C)              ok 
      8      air outlet                 32C (50C,64C,74C)              ok 
      9      air inlet                  25C (41C,56C,66C)              ok 
      9      air outlet                 34C (50C,64C,74C)              ok 
      10     air inlet                  25C (43C,58C,61C)              ok 
      10     air outlet (front)         25C (51C,66C,69C)              ok 
      10     air outlet (back)          26C (43C,58C,61C)              ok
      
      

      }}

      So for  example, the default value of 60ºC for a critical would be below the normal value for these metrics is throwing errors 5 - Air outlet, 5 XPP

      The most extreme case is the XPP value where the minor warning starts at 101ºC, and currently it's throwing errors on 60ºC.

      Having a higher preset value for this metric would be the appropiate such a $TEMP_CRIT:"XPP"

       